Chapter 5 iCOM Controller
Parameters
U202
RTN SNSR
U203
HI TEMP
U204
LO TEMP
U205
HI HUM
U206
LOW HUM
U207
SENSOR A
U208
HI TEMPA
U209
LO TEMPA
U210
HI HUM A
U211
LO HUM A
U213
SUP SNSR
U214
HI SUP T
U215
LO SUP T
To browse through the menu, press the enter button to highlight the option, and use the up or down button to
scroll.
Password is required for changing the setpoints. Then, enter the SET ALARMS menu, press the enter button
to highlight the option, use the up or down button to browse the submenu. Press the enter button to enter the
selected parameter. Use the up or down button to change the setpoints, and press the enter button to save the
change, or press the ESC button to quit the change.

5.6.6 SENSOR DATA

You can monitor the data acquired by the sensors through the SENSOR DATA menu. The values are read only,
no setting or change is allowed. The parameters are described in Table 5-7.
Parameters
U301
TEMP A
U302
HUM A
U303
TEMP B
U304
HUM B
U305
TEMP C
U306
HUM C
U307
FC TEMP
U308
AMB TEMP
U309
FC STATE
U310
DS1 TEMP
U311
DS2 TEMP
U313
Hi Te H
U313
Hi Te M
U313
Hi Te S
Table 5-6 Descriptions of SET ALARMS parameters
Default
Setting range
Yes
Yes, No
27°C
1°C ~ 99°C
18°C
1°C ~ 99°C
60%
1% ~ 99%
40%
1% ~ 99%
No
Yes, No
50°C
1°C ~ 99°C
25°C
1°C ~ 99°C
70%
1% ~ 99%
30%
1% ~ 99%
No
Yes, No
24°C
1°C ~ 99°C
10°C
1°C ~ 99°C
Table 5-7 Descriptions of SENSOR DATA parameters
Unit
Description
°C
Temperature of sensor A
Relative humidity of
%
sensor A
°C
Temperature of sensor B
Relative humidity of
%
sensor B
°C
Temperature of sensor C
Relative humidity of
%
sensor C
Free cooling
°C
temperature
°C
Outdoor temperature
-
Free cooling status
Temperature of digital
°C
scroll 1
Temperature of digital
°C
scroll 2
Daily high temperature
hr
(hour)
Daily high temperature
m
(minute)
Daily high temperature
s
(second)
Liebert.PEX Chilled Water Series Air Conditioner User Manual
Description
Return air alarm enable
High return air temperature alarm setpoint
Low return air temperature alarm setpoint
High return air humidity alarm setpoint
Low return air humidity alarm setpoint
Sensor A alarm enable
High temperature alarm setpoint of sensor A
Low temperature alarm setpoint of sensor A
High humidity alarm setpoint of sensor A
Low humidity alarm setpoint of sensor A
Supply air alarm enable
High supply air temperature alarm setting value
Low supply air temperature alarm setting value
Parameters
Unit
U313
Hi Temp
°C
U314
Lo Te H
U314
Lo Te M
m
U314
Lo Te S
U314
Lo Temp
°C
U315
Hi Hu H
U315
Hi Hu M
m
U315
Hi Hu S
U315
Hi Humi
%
U316
Lo Hu H
U316
Lo Hu M
m
U316
Lo Hu S
U316
Lo Humi
%
Description
Daily high temperature
Daily low temperature
h
(hour)
Daily low temperature
(minute)
Daily low temperature
s
(second)
Daily low temperature
h
Daily high humidity (hour)
Daily high humidity
(minute)
Daily high humidity
s
(second)
Daily high humidity
h
Daily low humidity (hour)
Daily low humidity (minute)
Daily low humidity
s
(second)
Daily low humidity

Hide quick links: