2.4 Piping

The pipes to connect include:
1. Water drain-pipe of the unit.
2. Water inlet pipe of infrared humidifier.
3. Chilled water inlet and outlet pipes.
Connecting the water drain-pipe of the unit
The condensing water of infrared humidifier and evaporator is converged by the cross connector and drains
through the drain pipe, as shown in Figure 2-24. The outer diameter (OD) of the pipe is 25mm. If the drain pipe
is used by three or more units, the minimal OD of the pipe should be 40mm.
Note
1. A Φ25 hose clamp is delivered as an accessory to connect the drain pipe.
2. Because the humidifier contains boiling water, the plastic pipe must be rated higher than 194°F.
3. When connecting the drain pipe, make sure that the U bend is installed vertically and the 'U' shape is not distorted, so as to
ensure that the cooling water can be drained immediately and effectively.
Humidifier water
tray drain pipe
Transportation
fixing board
Revolving axis (each
in left and right side)
Figure 2-22 Removing backward fan transportation fixing board and pallet
Pallet
Figure 2-23 Fan sinking under floor
Liebert.PEX Chilled Water Series Air Conditioner User Manual
Pallet
Fixing screws (2 pcs)
Chapter 2 Mechanical Installation
Fixing screws (7 pcs)
Handle
Back ward fan
Pallet
Fan protective screening
Fixing screws (5 pcs)
Backward fan
19