2. Too small space for the indoor unit will baffle the airflow, shorten the cooling cycle; the air supply and air
exhaust may mix, and the decibel may rise.
3. Do not place the indoor unit in a concave or at the end of a strip area.
4. Do not huddle multiple indoor units, lest there should be mixed airflow, unbalanced load and competitive
operation.
5. For the convenience of daily maintenance, do not install other equipment (such as smoke detector) above
the cabinet.
6. Backward fan downflow unit: because the fan needs to sink during the operation, so the floor must be
higher than 400mm.
Figure 2-17 shows the installation place of the indoor unit.
Maintenance space requirement
Leave more than 600mm of maintenance space in the front and on both sides of the chilled water AC unit, as
shown in Figure 2-17.

2.3.2 Installation Procedures

The installation procedures of indoor unit are as follows:
1. Make the mounting base according to the dimensions in Figure 2-18, Figure 2-19 and Figure 2-20 and the
requirements in Table 2-3. You can make it yourself or contact Emerson Network Power Co., Ltd. for
non-standard production.
600
Unit
Note:
The reserved maintenance space during the installation
Figure 2-17 Installation place of indoor unit (unit: mm)
Rubber cushion
Installation hole
(lateral)
for expansion bolt
Rear side of cabinet
Figure 2-18 Mounting base of one-bay series (unit: mm)
Liebert.PEX Chilled Water Series Air Conditioner User Manual
Chapter 2 Mechanical Installation
Good place
Unit
600
600
Bad place
Front side of cabinet
Rubber cushion (top)
Angle steel
4- Ф 14 cabinet installation hole
Φ
S teel plate
Rubber cushion (bottom)