3. Click the Access on SNMP at the left hand of the interface, as shown in Figure 6-11. Type user name
'Liebert' and password 'Liebert' and click the OK button to enter the setting interface of configure. Note that
the user name and password are case-sensitive.
4. Configure the Network Management System (NMS) of the host monitoring center in Figure 6-12. Click the
Edit button and type the IP address of the NMS in IP Address. Select the 'read' or 'write' in Access, type
'Public' in Community and then click the Save button.
Note
1. Before setting the NMS, the Edit button is displayed in the interface. After editing the configuration, the Edit button will
become the Save button.
2. After the NMS is configured, you must click the Save button to save the setting.