Chapter 5 iCOM Controller
Parameters
U401
LANGUAG
U402
YEAR
U402
MONTH
U402
DAY
U403
HOUR
U403
MINUTE
U403
SECOND
U404
TEMP F/C
U405
CONTRAST
U406
BUZ FREQ
U406
BUZ TEST
U407
BACKLITE
U408
SCREEN
U409
SHOWS
U410
DISPLAY
U411
DATE

5.6.8 TOTAL RUN HRS

The TOTAL RUN HRS menu records the total run time (unit: hr) of the system components. You can also set
the run time limits of the system components through this menu. If the actual component run time exceeds
the set limit, alarms will be raised.
This menu requires password. You can reset the total run time to zero in order to restart timing.
Note
Resetting the timers is not needed unless the components are replaced.
The parameters on this menu are described in Table 5-9. Each component has a LIMIT option to set the run
time limit of the corresponding component.
Parameters
U502
MOTOR(S)
U502
LIMIT
U503
COMP1
U503
LIMIT
U504
COMP2
U504
LIMIT
U505
CW/FC
U505
LIMIT
U506
HG/HW
U506
LIMIT
Table 5-8 Descriptions of DISPLAY SETUP parameters
Default
Setting range
RUS, CZE, CHI,
EN
ESP, FRE, ITA,
DEU, EN, POR
2005
-
04
01 ~ 12
19
01 ~ 31
19h
-
8min
-
17s
-
°C
°F, °C
50%
0% ~ 100%
50%
0% ~ 100%
Off
On, Off
5min, 10min,
5min
30min, 1hr, 12hr
Graph, Simple,
Graph
SimCo, GraCo
A + S
SET, ACT, A + S
Norm
Norm (normal), Inv
m/d/y, d.m.y,
m/d/y
y-m-d
Table 5-9 Descriptions of TOTAL RUN HRS parameters
Default
Related component
1000hr
Fan motor
32000hr
500hr
Compressor 1
32000hr
500hr
Compressor 2
32000hr
1000hr
Chilled water/free
32000hr
cooling
23hr
Hot gas/hot water
32000hr
Liebert.PEX Chilled Water Series Air Conditioner User Manual
Description
Language options
Current year
Current month
Current day
Current hour
Current minute
Current second
Temperature indication
Display contract
Buzzer frequency. 0% means buzzer silenced
Buzzer frequency test switch. It determines whether or not
there will be sound accompanying the adjustment of BUZ
FREQ through the setting
Backlight time, or the backlight time when there is no button
operation
Main interface display mode
Main interface display mode of setpoints and actual values.
Range:
SET: only setpoints of the temperature and humidity are
displayed.
ACT: only actual temperature and humidity are displayed.
A + S: both setpoints and actual values of the temperature
and humidity are displayed
Display color
Date display format
Parameters
U507
EL HEAT1
U507
LIMIT
U508
EL HEAT2
U508
LIMIT
U509
EL HEAT3
U509
LIMIT
U510
HUM
U510
LIMIT
U511
DEHUM
U511
LIMIT
Default
Related component
34hr
Electric heater 1
32000hr
45hr
Electric heater 2
32000hr
0hr
Electric heater 3
32000hr
7hr
Humidifier
32000hr
1hr
Dehumidification
32000hr

Hide quick links: