Emerson Chilled Water Series User Manual page 63

Chilled water air conditioner
Table of Contents

Advertisement

56
Chapter 5 iCOM Controller
A110
CAP TYPE
A111
FLOCT
Other settings
Parameters (3/9)
A113
DS CYCLE
A114
DS HT
A115
DS SWB
A116
LP TYPE
A117
LP PH1
A118
LP PH2
A119
LC PRE
A120
LC POST
A121
CHARGE P
4step,
No
HGBP, DS,
DS + TH, No
0s
0 ~ 180s
Table 5-31 Descriptions of other settings
Default
Setting range
s
-
°C
-
°C
-
Analog
Analog, Digital
ps
-
ps
-
0.0s
-
0.0s
-
br
-
Liebert.PEX Chilled Water Series Air Conditioner User Manual
Capacity control type. 4step: four steps. HGBP: hot gas bypass. DS:
digital scroll. DS + TH: digital scroll and temperature switch. No:
with no need for capacity control type
Shutdown time of airflow loss
Digital scroll cycle
Digital scroll high temperature
Digital scroll switchback
Low pressure device type
Low pressure threshold phase 1
Low pressure threshold phase 2
Liquid control pre-time
Liquid control post-time
Loss of Charge Protection
Description

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Liebert pex p3110vc2ms1rz00

Table of Contents