Emerson Chilled Water Series User Manual page 64

Chilled water air conditioner
Table of Contents

Advertisement

LP sensor related settings
Parameters (4/9)
A124
LP1 LOW
A124
LP1 LOW
A125
LP1 HIGH
A125
LP1 HIGH
A126
LP1 ACT
A127
LP2 LOW
A127
LP2 LOW
A128
LP2 HIGH
A128
LP2 HIGH
A129
LP2 ACT
A130
PD CUT
A131
PD RECYC
A132
HEAT REJ
Free-cooling, HG and HW related settings
Table 5-33 Descriptions of free-cooling, HG and HW related settings
Parameters (5/9)
A135
K11 ACT
A136
C/W F DUR
A137
COOL TYP
A138
STOP FC+
A139
FC F DUR
A140
FC F K11
A141
COMP + FC
A142
HW F DUR
A143
HG HEAT
A144
HEAT OP
Humidification and dehumidification related settings
Table 5-34 Descriptions of humidification and dehumidification related settings
Factory 6/9
A146
HUM TYPE
A147
HUM VOLT
A148
HUM LAST
A149
PREFILL
A150
FILL
A151
HUM ON
A152
DEH COMP
Liebert.PEX Chilled Water Series Air Conditioner User Manual
Table 5-32 Descriptions of LP sensor related settings
Default
Setting range
10%
0 ~ 100%
0bbr
10 ~ 50br
90%
0 ~ 100%
10.3br
10 ~ 50br
-
-
10%
0 ~ 100%
0br
10 ~ 50br
90%
0 ~ 100%
10.3br
10 ~ 50br
-
-
br
-
br
-
FSC, L-T,
W/G
W/G
Default
Setting range
WNG 、 DEH 、 NOP 、 FC
DEH
3min
1min ~ 3min
SINGL
Singl, FC, DC
°C
-
0min
1min ~ 3min
Yes
Yes, No
No
Yes, No
3min
0 ~ 3min
No
Comp.1, Comp.2, No
STAGE
Stage, Delay, No
Default
Setting range
External, IFS, IFL,
PEX6, PEX9, PEX12,
21LLA, 53LLC,
IFS
53HLB, 93LLE,
93HLD, d3H, HT2,
HT5, HT9, SGH, No
V
-
15hr
-
30s or 57s
-
57s
-
584s
-
1
1, 2, both
Chapter 5 iCOM Controller
LP1 sensor lower threshold (percentage)
LP1 sensor lower threshold
HP1 sensor lower threshold (percentage)
HP1 sensor lower threshold
Actual LP1 signal. Read only
LP2 sensor lower threshold (percentage)
LP2 sensor lower threshold
HP2 sensor lower threshold (percentage)
HP2 sensor lower threshold
Actual LP2 signal. Read only
Pumpdown cutout
Pumpdown recycle
Heat rejection control. Range:
FSC: fan speed control; L-T: Lee-Temp; W/G: water/glycol cooling
-
Cooling water flush duration
Three cooling type
Stop FC at setpoint + or value
Freecooling flush duration
Freecooling flush starts R5
Compressor plus FC simultaneously
Hot water flush duration
Hot gas heating enabled
Electric heater operation mode
Humidifier model
-
Detect whether the last operation time exceeds this
cycle setting during the startup of the humidifier. Unit:
hr
Prefill time. Unit: second
Fill time. Unit: second
Humidifier on time. Unit: second
Dehumidification with compressor. When 1 or 2 is
selected, compressor 1 or 2 is used for
dehumidification. When Both is selected, the two
compressors are both used for dehumidification
Description
Description
Description
57