Emerson Chilled Water Series User Manual page 58

Chilled water air conditioner
Table of Contents

Advertisement

C1 ACT, C2 ACT, C3 ACT and C4 ACT correspond to the customer alarms. 'OPEN' means normally open,
'CLOSE' means normally closed.
Alarm delays setting
The alarm delays are the time after faults occur and before the alarms are triggered. See Figure 5-9 for the
menu format.
The alarm name, delay time, delay enabling and alarm type are displayed from left to right in the list.
The alarm delay can be set to 0 ~ 9999. Unit: second.
The delay enabling determines whether the alarm will be displayed and the alarm menu is entered, Options
include 'Yes' and 'No'.
The alarm type can be set to 'ALM' (alarm), 'WRN' (warning) and 'MSG' (message). They determine the alarm
degree of the corresponding event.
The alarm names are listed in Table 5-25.
Alarm/event
SN
name
S236
FOL
S237
LOA
S238
CF
S239
HRT
S240
LRT
S241
HRH
S242
LRH
S243
HTA
S244
LTA
S245
HHA
S246
LHA
S249
OL1
S250
OL2
S251
HP1
S252
HP2
S253
LP1
S254
LP2
S255
PD1
S256
PD2
S257
HT1
S258
HT2
S259
EHO
S262
WHE
S263
SMO
S264
WUF
S265
CPH
Liebert.PEX Chilled Water Series Air Conditioner User Manual
SET ALARMS
S236
FOL
S237
LOA
S238
CF
S239
HRT
S240
LRT
S241
HRH
Figure 5-9 Alarm delay
Table 5-25 Alarm name description
Description
Fan overload
Loss of airflow
Filter clogged
High room temp.
Low room temp.
High room hum.
Low room hum.
High temperature of sensor A
Low temperature of sensor A
High humidity of sensor A
Low humidity of sensor A
Compressor 1 overload
Compressor 2 overload
Compressor 1 high pressure
Compressor 2 high pressure
Compressor 1 low pressure
Compressor 2 low pressure
Compressor 1 pumpdown
fails
Compressor 2 pumpdown
fails
Digital scroll 1 high
temperature
Digital scroll 2 high
temperature
EL HEAT HIGH TEMP
Working hours exceeded
Smoke detected
Water under floor
Conderser pump high water
Chapter 5 iCOM Controller
2/10
01
T
DEL
EN
5
Yes
ALM
3
Yes
ALM
2
Yes
WRN
30
Yes
WRN
Yes
30
WRN
30
Yes
WRN
Alarm/event
SN
name
S266
LOF
S267
SGP
S268
STB
S269
HUP
S270
NOC
S271
-
S272
LOP
S275
CI1
S276
CI2
S277
CI3
S278
CI4
S279
CS
S280
HTD
S281
LB1
S282
RL
S283
HL
S284
FCL
S285
CL
S288
SC1
S289
SC2
S290
NOP
S291
CN1
S292
CN2
S293
EFF
S294
HST
S295
LST
Description
Loss of flow
Standby glycol pump on
Standby unit on
Humidifier problem
No connection w/Unit1
No connection w/UnitX
LOSS OF POWER
Customized input 1
Customized input 2
Customized input 3
Customized input 4
Call for service
High temperature
Loss of air blower 2
Reheat lockout
Humidifier lockout
FC lockout
Compressor(s) lockout
Short cycle 1
Short cycle 2
NO power
Condensor 1 Fail
Condensor 2 Fail
EC Fan fail
High supply air temperature
Low supply air temperature