Diagnostics - Emerson Chilled Water Series User Manual

Chilled water air conditioner
Table of Contents

Advertisement

48
Chapter 5 iCOM Controller
Parameters
S081
AVG RUN
S082
BEST
S083
WORST
S084
ALARMS
S085
BONUS

5.7.5 DIAGNOSTICS

The DIAGNOSTICS menu is classified into two groups. After entering the menu, pressing the up button and
down button can switch between two groups and pressing the enter button can enter the parameters of the
corresponding group. The parameters of group 1 are settable and used to help the maintenance personnel
start and cut off devices by hand in site, so as to realize the diagnosis for devices. The parameters of group 2
are read only and reflect the fault condition of the devices. See Table 5-22 for detailed descriptions.
Parameters
S302
S303
S304
S305
S306
S307
S308
S309
S310
S311
S313
S314
Group 1
S315
S315
S316
S317
S318
S319
S319
S320
S321
S322
S324
Default
min
Average humidifier run time calculated through the number of starts and run hours
24
Starts per day best
240
Starts per day worst
0
Number of high pressure alarms since the last maintenance
Bonus amount. Actual bonus calculated through the number of starts and average run
0MM
time. This value determines the time for the next maintenance
Table 5-22 Descriptions of DIAGNOSTICS parameters
Default
HP1 CODE
0
HP2 CODE
0
HT1 CNT
0
HT2 CNT
0
LP1 CODE
0
LP2 CODE
0
LP1 ACT
br
LP2 ACT
br
LP1 ACT
br
LP2 ACT
br
MANUAL
No
MOTOR(S)
On
COMP1
Off
C1 MODE
Run
C1 CAP
Off
C1 CYCLE
0%
LLSV 1
Off
COMP2
Off
C2 MODE
Run
C2 CAP
Off
C2 CYCLE
0%
LLSV2
Off
EL HEAT1
Off
Liebert.PEX Chilled Water Series Air Conditioner User Manual
Description
Setting
range
HP 1 alarm counting. The counter can be reset to 0
-
through the parameter
HP 2 alarm counting. The counter can be reset to 0
-
through the parameter
HT 1 alarm counting. The counter can be reset to 0
-
through the parameter
HT 2 alarm counting. The counter can be reset to 0
-
through the parameter
LP 1 alarm counting. The counter can be reset to 0
-
through the parameter
LP 2 alarm counting. The counter can be reset to 0
-
through the parameter
-
Actual LP 1
-
Actual LP 2
-
Actual LP 1
-
Actual LP 2
Selecting 'Yes' can turn on or off the components;
Yes, No
selecting 'No' can prohibit manual setting
Diagnosis switch of fan motor. The settings 'On' and 'Off'
On, Off
are used to manually start and shut down the fan
respectively
Diagnosis switch of compressor 1. The 'On' setting of this
On, Off
parameter can start compressor 1 only when the fan has
been started
Run, Evac,
Compressor 1 operation mode selection
Charg
Refrigeration capacity output of digital scroll compressor
On, Off
1
-
-
On, Off
Diagnostic of liquid line solenoid valve of compressor 1
Diagnostic swtich of compressor 2. Note that the On
On, Off
setting of this parameter can start compressor 2 only
when the fan has been started
Run, Evac,
Compressor 2 operation mode selection
Charg
Refrigeration capacity output of digital scroll compressor
-
2
-
-
Diagnosis switch of liquid line solenoid valve of
On, Off
compressor 2
Diagnosis switch of electric heater 1. The 'On' setting of
On, Off.
this parameter can start electric heater 1 only when the
Description