28
Chapter 3 Electric Installation
Figure 3-4 Amplified figure of power interface
Note
The cable sizes should meet the local wiring rules.
Model
P1020
P1030
P1040
P1050
P2050
P2070

3.2.3 Connecting Control Cables

The control interfaces are located as shown in Figure 3-1, Figure 3-2 and Figure 3-3. The control interface is
amplified in Figure 3-6. The upper part of the terminal block is connected to the AC unit, while the lower part is
used as user control signal interfaces.
Note
Before connecting the control cables, the wiring personnel must take antistatic measures.
N
PE
N
PE
L1
L2
L3
L1
L2
L3
N
PE
Table 3-1 Maximum operation current of AC unit
Maximum operation current (A)
13.1
13.1
13.1
13.1
23.5
23.5
Connecting with
Connecting
smoke sensor, 91# is
with common
its common terminal
alarm
Alarm output of
smoke sensor
Figure 3-6 Wiring of control interfaces
Liebert.PEX Chilled Water Series Air Conditioner User Manual
Cable clamp
Model
P2090
P2100
P3110
P3140
P3150
50,51,55 is defined
50,51,52 are defined
alarm terminals, 24# is
its common terminal
Short connecting line, no
short line if the remote
shut down is connected
Figure 3-5 Cable clamp
Maximum operation current (A)
23.5
23.5
28.2
28.2
28.2