OPERATION
46
EATON Powerware
6.
Configure the UPS for parallel operation through the front panel:
S
Press any button on the front panel display to activate the menu
options.
S
Using the
button, scroll to the Settings menu, and then press
the
button twice to select the User Settings menu.
S
Using the button, scroll to the Parallel Operation Settings
option and press the
S
Press the
button to select the Parallel Unit Number option.
S
Use the button to scroll the Unit number to identify the UPS
number of the parallel system (Unit #1, Unit #2, or Unit #3).
S
Press the
button to save the setting.
S
Use the button to scroll to the Parallel Operation Mode option
and press the
S
Use the button to scroll the desired option (either Redundant
Mode or Capacity Mode).
S
Press the
button to save the setting.
ESC
7.
Press the
button until the Eaton Powerware logo appears.
8.
Repeat Steps 6 and 7 for the remaining UPSs in the parallel system.
®
9155 Parallel UPS (8–15 kVA) User's Guide
button.
button to enter the menu.
S