Eaton Powerware 9155 User Manual page 54

Parallel ups 8–15 kva
Hide thumbs Also See for Powerware 9155:
Table of Contents

Advertisement

OPERATION
48
EATON Powerware
17. Select the System On option; press the
18. Confirm the selection. Press and hold the
seconds, until the UPS stops beeping.
The UPS goes to Bypass mode for five seconds, and then the
indicator illuminates. Each UPS should be in Normal mode.
ESC
19. Press the
button until the Eaton Powerware logo appears.
20. Auto-calibrate the load (with 10% minimum load recommended):
S
Using the
button, scroll to the Settings menu and then press
the
button twice to select the User Settings menu.
S
Using the button, scroll to the Parallel Operation Settings
option and press the
S
Using the button, scroll to the Start Auto Calibration option and
press the
button to select the option. Press and hold the
button for a second to begin the process.
21. After calibration completes (in less than a minute), verify the load
sharing through the front panel:
S
Using the button, scroll to the Measurements menu and press
the
button twice to select the Parallel System menu.
S
Select and view the voltage meter options.
ESC
22. Press the
button until the Eaton Powerware logo appears.
®
9155 Parallel UPS (8–15 kVA) User's Guide
button.
button for three
button.
S
164201592 C www.eaton.com/powerquality

Advertisement

Table of Contents
loading

Table of Contents