Wall Mounted Type - Daikin RXYQ72 Serivce Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

SiUS39-601

Wall Mounted Type

Model
1 Cooling Capacity
2 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Rows × Stages × FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Fan
Motor Output
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
4 Sound Level (H)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
Specifications
FXAQ07MVJU
Btu/h
7,500
Btu/h
8,500
White (3.0Y8.5/0.5)
in
11–3/8×31–1/4×9
2×14×17
ft²
1.73
QCL9661M
Cross Flow Fan
HP
0.054
cfm
260/160
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ
in
1/4 (Flare Connection)
φ
in
1/2 (Flare Connection)
VP13
in
(External Dia. 11/16 Internal Dia. 1/2)
Lbs
25
dBA
36
Fuse
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tube, Clamps,
Screws.
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25ft (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
FXAQ09MVJU
9,500
10,500
White (3.0Y8.5/0.5)
11–3/8×31–1/4×9
2×14×17
1.73
QCL9661M
Cross Flow Fan
0.054
280/175
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ
1/4 (Flare Connection)
φ
1/2 (Flare Connection)
VP13
(External Dia. 11/16 Internal Dia. 1/2)
25
37
Fuse
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tube, Clamps,
Screws.
C:3D046038A
Specifications
FXAQ12MVJU
12,000
13,500
White (3.0Y8.5/0.5)
11–3/8×31–1/4×9
2×14×17
1.73
QCL9661M
Cross Flow Fan
0.054
300/180
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ
1/4 (Flare Connection)
φ
1/2 (Flare Connection)
VP13
(External Dia. 11/16 Internal Dia. 1/2)
25
38
Fuse
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tube, Clamps,
Screws.
19