Daikin RXYQ72 Serivce Manual page 99

R-410a heat pump 60hz
Table of Contents

Advertisement

Field Setting
Push the SET button and match with the LEDs No. 1 - 15, push the RETURN button, and enter
the data for each setting.
expressing are as follows:
88
Data such as addresses and number of units is expressed as binary numbers; the two ways of
9 797997
16
4
1
32
8
2
977 7979
64
16
No.12
128 32
977 7997
4
1
No.13
8
2
See the preceding page for a list of data, etc. for No. 0 - 22.
The No. 1 cool/heat unified address is expressed as a binary number
consisting of the lower 6 digits. (0 - 63)
In
the address is 010110 (binary number), which translates to 16 +
4 + 2 = 22 (base 10 number). In other words, the address is 22.
The number of terminal blocks for No. 12 and 13 is expressed as an
8-digit binary number, which is the combination of four upper, and
four lower digits for No. 12 and 13 respectively. (0 - 128)
In
the address for No. 12 is 0101, the address for No. 13 is 0110,
and the combination of the two is 01010110 (binary number), which
translates to 64 + 16 + 4 + 2 = 86 (base 10 number). In other words,
the number of terminal block is 86.
SiUS39-601