Field Setting
b. "Setting mode 2"
Push and hold the MODE button
(BS1) for 5 seconds and set to
"Setting mode 2".
<Selection of setting items>
Push the SET button (BS2) and set
the LED display to a setting item
shown in the table on the right.
Push the RETURN button (BS3) and
decide the item. (The present setting
condition is blinked.)
<Selection of setting conditions>
Push the SET button (BS2) and set
to the setting condition you want.
Push the RETURN button (BS3) and
decide the condition.
Push the RETURN button (BS3) and
set to the initial status of "Setting
mode 2".
∗ If you become unsure of how to
proceed, push the MODE button
(BS1) and return to setting mode 1.
84
No.
Setting item
EMG (Emergency
0
operation 1)
Cool/heat unified
1
address
Low noise/demand
2
address
Indoor unit forced
5
fan H
Indoor unit forced
6
operation
8
Te setting
9
Tc setting
Defrost changeover
10
setting
Sequential operation
11
setting
External low noise
12
setting / Demand
setting
13
AIRNET address
High static pressure
18
setting
Emergency
operation
19
(STD compressor
operation prohibited)
Additional refrigerant
20
charge operation
setting
Refrigerant recovery /
21
vacuuming mode
setting
Night-time low noise
22
setting
25
Low noise setting
Night-time low noise
26
control starting
setting
Night-time low noise
27
control ending
setting
(V2764)
Power transistor
check mode
∗Check after
28
disconnection of
compressor wires
Capacity
29
precedence setting
30
Demand setting 1
Normal demand
32
setting
Description
Operates by Standard compressor only when inverter
compressor malfunctions. Temporary operation until the
compressor is replaced. Since the comfortability is
extremely deteriorated, immediately replace the
compressor.
Sets address for cool/heat unified operation.
Address for low noise/demand operation
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
Allows forced operation of indoor unit.
Target evaporation temperature for cooling
Target condensation temperature for heating
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
Sets sequential operation
Reception of external low noise or demand signal
Set address for AIRNET.
Make this setting in the case of operating in high static
pressure mode with diffuser duct mounted.
Used to operate system only with inverter compressor when
STD compressor malfunctions. This is a temporary
operation extremely impairing comfortable environment.
Therefore, prompt replacement of the compressor is
required.
Carries out additional refrigerant charge operation.
Sets to refrigerant collection mode.
Sets automatic nighttime low noise operation in a simple
way.
The operating time is based on "Starting set" and "Ending
set".
Sets low noise level when the low noise signal is input from
outside.
Sets starting time of nighttime low noise operation.
(Nighttime low noise setting is also required.)
Sets ending time of nighttime low noise operation.
(Nighttime low noise setting is also required.)
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PC board.
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out
low noise operation and nighttime low noise operation.
Changes target value of power consumption when demand
control 1 is input.
Normally enables demand control 1 without external input.
(Effective to prevent a problem that circuit breaker of small
capacity is shut down due to large load.
SiUS39-601