M8" Malfunction Of Transmission Between Optional Controllers For Centralized Control - Daikin RXYQ72 Serivce Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

SiUS39-601
"M8"
4.3
Malfunction of Transmission Between Optional
Controllers for Centralized Control
M8
Remote
Controller
Display
Applicable
Schedule timer
Models
Method of
Detect the malfunction according to DIII-NET transmission data. (The system will be automatically
reset.)
Malfunction
Detection
Malfunction
When no master controller at the time of the startup of slave controller.
When the optional controllers for centralized control which was connected once, shows no
Decision
response.
Conditions
Supposed
Causes
Troubleshooting
Malfunction of transmission between optional controllers for centralized control
Defect of PC board of optional controllers for centralized control
Troubleshooting (OP: Schedule Timer)