J6" Outdoor Unit: Malfunction Of Thermistor (R4T) For - Daikin RXYQ72 Serivce Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
2.27 "J6" Outdoor Unit:
Outdoor Unit Heat Exchanger Deicer
J6
Remote
Controller
Display
Applicable
RXYQ72M, 96M
Models
Method of
Malfunction is detected from the temperature detected by the heat exchanger thermistor.
Malfunction
Detection
Malfunction
When a short circuit or an open circuit in the heat exchange thermistor is detected.
Decision
Conditions
Supposed
Causes
Troubleshooting
154
Malfunction of Thermistor (R4T) for
Defect of thermistor (R4T) for outdoor unit coil
Defect of outdoor unit PC board (A1P)
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Connector
is connected to X37A
of outdoor unit PC
board (A1P).
YES
Resistance
is normal when
measured after
disconnecting the thermistor
R4T from the indoor
unit PC board.
(3.5kΩ~
360kΩ)
1
*
YES
1: Refer to thermistor resistance / temperature characteristics table on P239.
NO
NO
SiUS39-601
Connect the thermistor and turn
on again.
Replace the thermistor R4T.
Replace outdoor unit PC board
(A1P).
(V3074)
Troubleshooting