Improper Combination Of Optional Controllerslers For Centralized Controllers; Ma" Improper Combination Of Optional Controllers For Centralized Control - Daikin RXYQ72 Serivce Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

SiUS39-601
"MA"
3.3
Improper Combination of Optional Controllers for
Centralized Control
MA
Remote
Controller
Display
Applicable
Central remote controller
Models
Method of
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Detection
Malfunction
When the schedule timer is set to individual use mode, other central component is present.
When multiple master controller are present.
Decision
When the remote control adapter is present.
Conditions
Supposed
Causes
Troubleshooting
Improper combination of optional controllers for centralized control
More than one master controller is connected
Defect of PC board of optional controller for centralized control
Troubleshooting (OP: Central Remote Controller)
197

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents