Low Pressure Protection Control - Daikin RXYQ72 Serivce Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

Protection Control
4.2

Low Pressure Protection Control

This low pressure protection control is used to protect compressors against the transient decrease
of low pressure.
[In cooling operation]
Low pressure not limited
Pe<50 psi
Low pressure limited
All STD compressors
Pe<36 psi
Master unit:52 Hz + OFF
Slave unit:Stop
Pe<10 psi
[In heating operation]
Pe<23 psi
124 Hz + OFF
Pe<23 psi
Pe<19 psi
52 Hz + OFF
50
Pe>58 psi
stop.
Low pressure standby
Low pressure not limited
Low pressure limited
Low pressure standby
Pe: LP pressure sensor detection
When occurring 3 times within 30 min.,
the malfunction code " E4 " is output.
Pe >36 psi
&
INV upper limit frequency = 210 Hz
Pe>28 psi
Pe<10 psi
When occurring 3 times within 30 min.,
the malfunction code "E4" is output.
value for master unit
Pe: LP pressure sensor detection
value for each outdoor unit
INV upper limit frequency: 1-step /
20 sec up from current compressor
frequency
SiUS39-601