Floor Standing Type - Daikin RXYQ72 Serivce Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

SiUS39-601

Floor Standing Type

Model
1 Cooling Capacity
2 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Rows × Stages × FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Fan
Motor Output
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
4 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.
Notes:
Specifications
FXLQ12MVJU
Btu/h
12,000
Btu/h
13,500
Ivory White (5Y7.5/1)
in
23–5/8×44–7/8×8–3/4
3×14×17
ft²
2.15
2D14B13
Sirocco Fan
HP
0.034
cfm
280/210
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
φ
in
1/4 (Flare Connection)
φ
in
1/2 (Flare Connection)
φ
in
27/32 O.D (Vinyl Chloride)
Lbs
66
dBA
36
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers, Level
Adjustment Screw.
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25ft (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
FXLQ18MVJU
18,000
20,000
Ivory White (5Y7.5/1)
23–5/8×55–7/8×8–3/4
3×14×17
3.04
2D14B20
Sirocco Fan
0.047
490/380
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
φ
1/4 (Flare Connection)
φ
1/2 (Flare Connection)
φ
27/32 O.D (Vinyl Chloride)
80
40
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Insulation for Fitting, Drain Hose,
Clamps, Screws, Washers, Level
Adjustment Screw.
3D045640
Specifications
FXLQ24MVJU
24,000
27,000
Ivory White (5Y7.5/1)
23–5/8×55–7/8×8–3/4
3×14×17
3.04
2D14B20
Sirocco Fan
0.047
560/420
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
φ
3/8 (Flare Connection)
φ
5/8 (Flare Connection)
φ
27/32 O.D (Vinyl Chloride)
80
41
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Insulation for Fitting, Drain Hose,
Clamps, Screws, Washers, Level
Adjustment Screw.
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents