Daikin RXYQ72 Serivce Manual page 46

R-410a heat pump 60hz
Table of Contents

Advertisement

SiUS39-601
Compressor Operating Priority
Each compressor operates in the following order of priority.
INV:
Inverter compressor
STD1: Standard compressor 1
RXYQ72M
STEP
INV
STD1
1
52Hz
OFF
2
57Hz
OFF
3
62Hz
OFF
4
68Hz
OFF
5
74Hz
OFF
6
81Hz
OFF
7
88Hz
OFF
8
96Hz
OFF
9
104Hz
OFF
10
110Hz
OFF
11
116Hz
OFF
12
124Hz
OFF
13
133Hz
OFF
14
143Hz
OFF
15
158Hz
OFF
16
165Hz
OFF
17
177Hz
OFF
18
189Hz
OFF
19
202Hz
OFF
20
210Hz
OFF
21
52Hz
ON
22
74Hz
ON
23
96Hz
ON
24
116Hz
ON
25
133Hz
ON
26
158Hz
ON
27
177Hz
ON
28
202Hz
ON
29
210Hz
ON
Compressors are operated in the order of descending priorities.
Compressors may operate in a pattern other than those listed in above tables subject to the operating conditions.
Function
RXYQ72M
RXYQ96M
No. 1 No. 2
No. 1 No. 2
INV
STD1
INV
STD1
RXYQ96M
STEP
INV
1
52Hz
2
57Hz
3
62Hz
4
68Hz
5
74Hz
6
81Hz
7
88Hz
8
96Hz
9
104Hz
10
110Hz
11
116Hz
12
124Hz
13
133Hz
14
143Hz
15
158Hz
16
165Hz
17
177Hz
18
189Hz
19
202Hz
20
210Hz
21
52Hz
22
74Hz
23
96Hz
24
116Hz
25
133Hz
26
158Hz
27
177Hz
28
202Hz
29
210Hz
STD1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
Basic Control
35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents