Check Operation - Daikin RXYQ72 Serivce Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

SiUS39-601
1.1.3

Check Operation

* During check operation, mount front panel to avoid the misjudging.
* Check operation is mandatory for normal unit operation.
On completion of test operation, LED on outdoor unit PC board displays the following.
H3P ON: Normal completion
H2P and H3P ON: Abnormal completion
In the case of multi-outdoor-unit system, make setting on the master unit PC board. (Setting with
the slave unit is disabled.)
[LED display in the case of multi-outdoor-unit system] (Same as that in emergency operation)
Test Operation
(When the check operation is not executed, alarm code "U3" will be displayed.)
* Discriminate the operating status of the master unit/slave units through the following LED
display.
LED display (7:ON
H1P---H7P H8P
Master:
7777777
77
7777 7
Slave :
7777777 9 9
7777777
(Factory set)
Check the indoor unit remote controller for
abnormal display and correct it.
:OFF
:Blink)
7 7
9 9
Test Operation
65