Troubleshooting by Indication on the Remote Controller
2.32 "JC" Outdoor Unit:
JC
Remote
Controller
Display
Applicable
RXYQ72M, 96M
Models
Method of
Malfunction is detected from pressure detected by low pressure sensor.
Malfunction
Detection
Malfunction
When the suction pipe pressure sensor is short circuit or open circuit.
Decision
Conditions
Supposed
Causes
Troubleshooting
160

Malfunction of Suction Pipe Pressure Sensor

Defect of low pressure sensor system
Connection of high pressure sensor with wrong connection.
Defect of outdoor unit PC board.
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
The low
pressure sensor is
connected to X45A (blue)
of outdoor unit PC
board (A1P).
YES
The
relationship
between the ∗1
VH and low pressure is
normal (see ∗2) when voltage
is measured between X45A pins
(2) and (3) of outdoor unit
PC board (A1P)
(see ∗1).
NO
1: Voltage measurement point
2: Refer to pressure sensor, pressure/voltage characteristics table on P241.
NO
YES
SiUS39-601
Connect low pressure sensor
property and restart system.
Replace outdoor unit PC board
(A1P).
Replace the low pressure sensor.
Troubleshooting
(V2808)