Contents Of Control Modes - Daikin RXYQ72 Serivce Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

SiUS39-601
3.1.8 Setting of Operation Control Mode from Remote Controller
(Local Setting)
The operation control mode is compatible with a variety of controls and operations by limiting the
functions of the operation remote controller. Furthermore, operations such as remote controller ON/
OFF can be limited in accordance with the combination conditions. (Refer to information in the table
below.)
Centralized controller is normally available for operations. (Except when centralized monitor is
connected)

3.1.9 Contents of Control Modes

Twenty modes consisting of combinations of the following five operation modes with temperature
and operation mode setting by remote controller can be set and displayed by operation modes 0
through 19.
Test Operation
ON/OFF control impossible by remote controller
Used when you want to turn on/off by central remote controller only.
(Cannot be turned on/off by remote controller.)
OFF control only possible by remote controller
Used when you want to turn on by central remote controller only, and off by remote controller
only.
Centralized
Used when you want to turn on by central remote controller only, and turn on/off freely by
remote controller during set time.
Individual
Used when you want to turn on/off by both central remote controller and remote controller.
Timer operation possible by remote controller
Used when you want to turn on/off by remote controller during set time and you do not want to
start operation by central remote controller when time of system start is programmed.