Operation Mode - Daikin RXYQ72 Serivce Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

Operation Mode

1.

Operation Mode

Indoor unit stop or
thermostat OFF
Normal operation
• Compressor PI control
• Motorized valve PI control
• Protection control
32
Operation in
stop mode
Indoor unit thermostat ON
Pressure
equalization
prior to startup
Startup control
• Cooling startup
control
• Heating startup
control
Outdoor unit
rotation
Cooling or heating
operation
Yes
Oil return IN
conditions are met.
No
Yes
Defrost IN
conditions are met.
No
Yes
Operation mode
changeover
No
Malfunction/Standby
Indoor unit stop or
thermostat OFF
Indoor unit thermostat ON
Malfunction/Standby
Indoor unit stop or
thermostat OFF
Malfunction/
Standby
*)
In the event indoor unit stops or the thermostat
turns OFF while in oil return operation or
defrosting operation, pump-down residual
operation is performed on completion of the oil
return operation or defrosting operation.
Restart standby
(Compressor stop)
Pump-down
residual
operation
Oil return operation
Outdoor unit
rotation
Defrosting operation
SiUS39-601
Malfunction/
Standby
Function