List of Electrical and Functional Parts

3.

List of Electrical and Functional Parts

3.1

Outdoor Unit

3.1.1 RXYQ72M, 96MTJU
Item
Compressor
Inverter
STD.1
Crankcase heater (INV)
Crankcase heater (STD.1)
Crankcase heater (STD.2)
OC protection device for STD compressor
Fan motor
Motor
OC protection device
Functional parts Electronic expansion valve
(Main)
Electronic expansion valve
(Subcool)
Solenoid valve (Hot gas)
Solenoid valve (External multi oil)
Solenoid valve (Receiver gas charge)
Solenoid valve (Receiver gas discharge)
Solenoid valve (Non-operating unit gas discharge)
Solenoid valve (Non-operating unit liquid pipe close)
4 way valve
Pressure-related
Pressure switch (INV)
parts
Pressure switch (STD1)
Pressure switch (STD2)
Fusible plug
Pressure sensor (HP)
Pressure sensor (LP)
Thermistor
INV PCB
Main PCB
Others
Fuse (A1P)
230
Name
Type
Type
Cooling
Heating
Cooling
Heating
For fin
For outdoor air
For suction pipe
For discharge pipe (INV)
For discharge pipe (STD.1)
For discharge pipe (STD.2)
For heat exchanger
For subcooling heat exchanger
For receiver liquid pipe
For equalizing pipe
Symbol
M1C
M2C
E1HC
E2HC
E3HC
M1F
Y1E
Y2E
Y1S
Y2S
Y3S
Y4S
Y5S
Y6S
Y7S
S1PH
PS80 ON : 551+0/-21.8psi OFF : 413±21.8psi
S2PH
S3PH
FPGD-3D 158 to 167°F
S1NPH
PS8051A 0 to 601.9psi
S1NPL
PS8051A -14.5 to 246.6psi
R1T
R1T
R2T
R31T
R32T
R33T
R4T
R5T
R6T
R7T
F1, 2U
250VAC 10A Class B
SiUS39-601
Model
RXYQ72M, 96MTJU
JT100FCVDKT@3
JT170FCKTJ@3
240V 33W
240V 33W
28.8A
0.75kw
3.2A
0pls
PI control
PI control
0pls
TEV1620DQ2
TEV1620DQ2
TEV1620DQ2
VPV-603D
TEV1620DQ2
VPV-803DQ50
VHV0404
PS80
ON : 551+0/-21.8psi
OFF : 413±21.8psi
3.5 to 360Ω
3.5 to 360Ω
3.5 to 360Ω
3.5 to 400Ω
3.5 to 400Ω
3.5 to 400Ω
3.5 to 360Ω
3.5 to 360Ω
3.5 to 360Ω
3.5 to 360Ω