Specifications

Media Interface
Ethernet Specifications
Data Hiway Specifications
Power (Mains) Requirement
Electrical Connections
Dimensions
2000590-001
Advance Network Communication Board (ANCB): 10BASE-T RJ-45 STP
connector
Data rate:
Maximum Cable Length
Maximum length to adapter
concentrator/hub:
Cable Type (minimum req.):
Cable Characteristics:
248 Advance Units Maximum / 31 Units per Loop
8 Loops Maximum
Input Voltage
85-264 VAC, 47-63 Hz
Single Phase, Grounded Neutral
1 Ampere Maximum (<100 Watts)
Input Power
Terminal Strip for braided or solid 12 AWG (2.5mm
Data Hiway
Terminal Strip for dual or single pair Data Hiway cable
Interfaces
Laptop PC RS 232: 9-pin Sub D plug
Ethernet 10BASE-T: standard RJ-45 connector
Rack Mounted Package Configuration
See Figure 1-2 for Outline Drawing and Dimensions
Wall-Mounted Package Configuration
See Figure 1-3 for Outline Drawing and Dimensions
Zone 1 - Wall-Mounted Package Configuration
See Figure 1-4 for Outline Drawing and Dimension
10Mbits/sec.
Per Ethernet Specifications
100m (328 ft)
AT&T D-inside wire (DIW &
PDS, IBM Type 3, Category 3 or
5 data grade cabling)
100 Ohms nominal impedance
2
) maximum wire size
Advance Network Gateway