CE Installations,
16
Installation
Continued
3. A split ferrite must be clamped to Data Hiway cables and fixed im-
mediately to the outside of the ANG_EN; use Siemens Applied
Automation part number 1173000-013 ferrite contained in CE Instal-
lation Kit. This is required to meet the Conducted Immunity require-
ment for CE/EMC Heavy Industrial. All other CE/EMC Heavy Indus-
trial requirements are met without the use of a ferrite clamp.
4. Shielded Ethernet cable must be used for all Ethernet connections,
in and outside the GC, and coupled through the enclosure using a
shielded RJ-45 coupler; use Siemens Applied Automation part num-
ber 1183200-003 contained in CE Installation Kit. A mounting plate
(Siemens part number 2020261-001) is also available to accomplish
this. If needed for Zone 1 installation Siemens Applied Automation
part numbers 2017984-001 and 2017985-001 is available to maintain
purge. If a PG gland is used to make the 360-degree termination of
the Ethernet shield at the enclosure, the Installation Kit and other
parts are not required.
2000590-001