Technical Specifications Of Mindconnect Nano - Siemens MindConnect Nano Getting Started

Getting connected to mindsphere
Hide thumbs Also See for MindConnect Nano:
Table of Contents

Advertisement

A.2

Technical specifications of MindConnect Nano

Functions
Field protocol – S7
Field protocol – OPC UA
Configuration of data collection
Data buffering
Proxy support
DHCP support
Security
Supply voltage
Type of supply voltage
Current consumption
Mains buffering
Mains/voltage failure stored energy
time
Interfaces
USB port
PCIe slot
serial interface
Video interfaces
Graphics interface
Industrial Ethernet
Industrial Ethernet interface
Monitoring functions
Status LEDs
Fan
EMC
Interference immunity against discharge of static electricity
Interference immunity against
discharge of static electricity
Interference immunity to cable-borne interference
Interference immunity on supply
cables
Getting Connected to MindSphere
Getting Started, 05/2018
Siemens S7 (for S7-3xx / S7-4xx / ET-200s PLCs)
Part 8 of the OPC UA specification (Data Access)
With Asset Manager in MindSphere
Up to 500 MB buffering space for collected data
Yes
Yes
Connection outbound via HTTPS on port 443 to MindSphere only; no incoming
connection accepted SSL/TLS encryption of data in transit to MindSphere
24 V
max. 1.8 A at 24 V
20 ms
1x USB 3.0 / 3x USB 2.0
1x PCIe x1 (Disabled)
1x COM (Disabled)
1x DisplayPort (Disabled)
2x 1000 Mbit RJ45
Yes
No
±6 kV contact discharge acc. to IEC 61000-4-2; ±8 kV air discharge acc. to IEC
61000-4-2
±2 kV acc. to IEC 61000-4-4, burst; ±1 kV acc. to IEC 61000-4-5, surge
·
symmetric;
±2 kV acc. to IEC 61000-4-5, surge asymmetric;
·
A.2 Technical specifications of MindConnect Nano
Appendix
81

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mindconnect iot2040

Table of Contents