Technical Specifications - Siemens SIMATIC NET IE/WSN-PA Link Compact Operating Instructions

Industrial ethernet / wireless hart
Hide thumbs Also See for SIMATIC NET IE/WSN-PA Link:
Table of Contents

Advertisement

Available languages

Available languages

Technical specifications

IE/WSN-PA Link
The following technical specifications apply to the IE/WSN-PA Link:
Technical specifications
Order numbers
Attachment to Industrial Ethernet
Number
Design
Properties
Transmission speed
Attachment to Modbus
Number
Transmission speed
Design
Wireless interface
Antenna for device with order number
6GK1 411-6CA40-0AA0
Antenna connector for device with
order number
6GK1 411-6CA40-0BA0
Wireless technology and frequency
range
Update time (burst rate)
Maximum network size per IE/WSN-
PA Link
Delay with a network size of
Maximum distance from the IE/WSN-
PA Link to the next WirelessHART
field device
Reliability
Electrical data
External power supply
IE/WSN-PA Link
Compact Operating Instructions, 12/2012, A5E02509264-AD
6GK1 411-6CA40-0AA0
6GK1 411-6CA40-0BA0
2
RJ-45 jack
10100BASE-T / 100BASE-Tx, IEEE 802, half duplex/full duplex, autocrossover,
autonegotiation, autosensing
10/100 Mbps
2
Modbus RTU:
Terminals A + B
Number
Design
Number
Design
WirelessHART ™ 2.4 - 2.5 GHz DSSS
Can be set (up to 60 minutes)
100 field devices
100 field devices:
50 field devices:
100 m
> 99 %
Power supply
Permitted range
Design
57600, 38400, 19200 or 9600 bps
1
Integrated
1
N-Connect Female
max. 8 s
max. 4 s
24 VDC
12 ... 30 V
Terminal block, 2 terminals
5
81