Data Hiway Connections,
Instructions,
continued
22
Installation
Continued
Step
3.
Connect the Channel A Data Hiway cable to port 1, ADH +
and - terminals. Repeat for port 2 for Channel B Data Hi-
way Cable.
Data Hiway Port 1 &
2 Connections
Pin 1-ADH-A+
Pin 2-ADH-A-
Pin 3- Ground
Pin 4-ADH-B+
Pin 5-ADH-B-
Pin 6- Ground
Advance Data Hiway cable shields is grounded at one end
only. If ground is at ANG_EN end, use GND terminal.
4.
Perform Data Hiway Post Installation Test; refer to Appen-
dix A. How to Test the Data Hiway.
5.
Remove the ADH plug connector from board. Do not make
final connections until you have set the loop and unit num-
ber; see Chapter 3. Data Communications Setup
6.
You are now ready for the Ethernet connections; go to
Ethernet Connections, page 23.