Installing The Plc-5C Controllers - Allen-Bradley ControlLogix User Manual

Controlnet interface module
Hide thumbs Also See for ControlLogix:
Table of Contents

Advertisement

Installing the PLC-5C
Controllers
Install the PLC-5C controller in a 1771 I/O chassis.
PLC-5C Controller and 1771 I/O Chassis
Card Guides
1. Set the backplane switches in the I/O chassis so that you can download
the ladder logic programs in the example applications. Put switches 5
and 6 in the "on" position, and all of the others in the "off" position.
2. Set the PLC-5C ControlNet node addresses using the two 10-digit rotary
switches on top of the PLC-5C modules.
For the example applications use node addresses 11 and 16.
ControlNet PLC-5C controller's NET address = 11
20
20
30
30
10
10
40
40
00
00
50
50
60
60
90
90
80
80
70
70
3. Insert the PLC-5C into the 1771 chassis.
4. Connect the PLC-5C's ControlNet port to the ControlNet network.
See the ControlNet 1.5 PLC-5 Programmable Controller User
Manual, publication 1785-6.5.22, for further information.