Schedule the Network Using
RSNetWorx for ControlNet
3. Drill down the tree through the ControlNet driver and the 1756-CNB
module at node 1 to the controller in slot 0.
4. Highlight the controller and click on the Download button.
5. Minimize RSLogix5000.
Whenever you add or remove a remote I/O module you must run
RSNetWorx for ControlNet to transfer the new configuration data to
networked modules and establish a Network Update Time (NUT) for
ControlNet that is compliant with the desired communication options
specified for each module during configuration.
Perform the following steps to schedule and optimize the network:
1. Start the RSNetWorx for ControlNet software.
The RSNetWorx for ControlNet main window will appear.
2. From the Network menu, select New.
3. Check the Edits Enabled box and go Online
Adding an I/O Chassis to an Existing ControlNet Network
11-11
1756-6.5.3 - December 1999