This message writes the value of the
seconds clock (S:23) in the PLC-5/40C
on ControlNet network #1 into data file
N7:0 of the PLC-5/40C processor on
ControlNet network #2.
Port Number 2 is the ControlNet Port
PLC-5C to PLC-5C Unscheduled Messaging Over Two ControlNet Networks
Create the Ladder Program
1. Enter the following ladder program:
2. Double-click on Setup Screen in the MSG instruction.
The following window will appear.
3. Under the General tab in the message Setup Screen, enter the following
configuration:
In this field
This PLC
Communication Command
Data Table Address
Size in Elements
Port Number
Target Device
Data Table Address
MultiHop
Select
PLC5 Typed Write
S:23
1
2
N7:0
Yes
1756-6.5.3 - December 1999
9-3