11-16
Adding an I/O Chassis to an Existing ControlNet Network
Test the Example Application
1756-6.5.3 - December 1999
Use the following procedure to test the operation of the remote analog
output:
1. Connect a voltmeter across the channel 0 outputs of the 1756-OF6VI
analog output module as shown in the following figure:
1756-OF6VI
1
OUT-0
V
5
RTN-0
2. Restore the RSLogix5000 software and place the controller in Run
mode.
3. Measure the output voltage of channel 0. You should see it slowly rising
to approximately 10V, reset to zero, and start rising again, etc.
4. Verify that the digital I/O modules in the other remote chassis are still
working. See page 10-18.
Refer to the ControlLogix Analog I/O Modules User Manual, publication
1756-6.5.9, and the ControlLogix Digital I/O Modules User Manual,
publication 1756-6.5.8, for assistance in wiring and debugging the I/O
modules, if needed.
+
–