Jumper Settings - Daikin SUPER MULTI NX CTXS07JVJU Service Manual

Super multi nx g-series / j-series
Hide thumbs Also See for SUPER MULTI NX CTXS07JVJU:
Table of Contents

Advertisement

SiUS12-928_B
Wireless Remote
(1) Remove the cover and take it off.
(2) Cut the address setting jumper.
Controller
ARC452 series

5.2.4 Jumper Settings

For the location of the jumper, refer to the following pages.
Trial Operation and Field Settings
Jumper
ADDRESS
EXIST
1
CUT
2
Jumper (on indoor
unit PCB)
JB
Fan speed setting
when compressor
stops for thermostat
OFF. (effective only
at cooling operation)
JC
Power failure
recovery function
CTXS/FTXS series: page 18, 20, 23
CDXS/FDXS series: page 26, 28
ARC433 series
ADDRESS
EXIST
CUT
(R12065)
Function
When connected
(factory set)
Fan speed setting ;
Remote controller
setting
Auto-restart
Field Settings
1
2
(R6573)
When cut
Fan speed setting; "0" (The fan
stops.)
The unit does not resume
operation after recovering from a
power failure. Timer settings are
cleared.