Input Current Control; Freeze-Up Protection Control - Daikin SUPER MULTI NX CTXS07JVJU Service Manual

Super multi nx g-series / j-series
Hide thumbs Also See for SUPER MULTI NX CTXS07JVJU:
Table of Contents

Advertisement

Control Specification
3.5

Input Current Control

Outline
An input current is detected by the CT while the compressor is running, and the frequency upper
limit is set from the input current.
In case of heat pump models, this control which is the upper limit control of the frequency takes
priority over the lower limit control of four way valve operation compensation.
Detail
Frequency control in each zone
Stop zone
 After 2.5 seconds in this zone, the compressor is stopped.
Dropping zone
 The upper limit of the compressor frequency is defined as operation frequency – 2 Hz.
 After this, the output frequency is lowered by 2 Hz every second until it reaches the keep zone.
Keep zone
 The present maximum frequency goes on.
Reset zone
 Limit of the frequency is canceled.
Limitation of current dropping and stop value according to the outdoor temperature
 The current drops when outdoor temperature becomes higher than a certain level (depending
3.6

Freeze-up Protection Control

Outline
During cooling operation, the signals sent from the indoor units control the operating frequency
limitation and prevent freezing of the indoor heat exchanger. (The signals from the indoor units are
divided into zones.)
Detail
The operating frequency limitation is judged with the indoor heat exchanger temperature 2 seconds
after operation starts and 30 seconds after the number of operation room is changed.
59
Input current
on the model).
(Reference)
55.4°F (13°C)
Reset zone
44.6°F (7°C)
Up zone
41°F (5°C)
Keep zone
37.4°F (3°C)
Dropping zone
32°F (0°C)
Stop zone
Compressor Stop
Stop Zone
Dropping Zone
Keep Zone
Reset Zone
(R14912)
Indoor heat exchanger
thermistor temperature
SiUS12-928_B
(R17362)
Function and Control