Trial Operation

4. Trial Operation

Outline
1. Measure the power supply voltage and make sure that it falls in the specified range.
2. Trial operation should be carried out in either cooling or heating operation.
3. Carry out the trial operation in accordance with the operation manual to ensure that all functions
 The air conditioner requires a small amount of power in its standby mode. If the system is not to
 If the circuit breaker trips to shut off the power to the air conditioner, the system backs up the
In cooling operation, select the lowest programmable temperature; in heating operation, select the
highest programmable temperature.
 Trial operation may be disabled in either operation mode depending on the room temperature.
 After trial operation is complete, set the temperature to a normal level.
 For protection, the system does not start for 3 minutes after it is turned off.
Detail
ARC452 Series
(1) Press the [ON/OFF] button to turn on the system.
(2) Press the both of [TEMP] buttons and the [MODE] button at the same time.
(3) Press the [MODE] button twice.
(4) Press the [MODE] button and select the operation mode.
(5) Trial operation terminates in approx. 30 minutes and switches into normal mode. To quit a trial
259
and parts, such as louver movement, are working properly.
be used for some time after installation, shut off the circuit breaker to eliminate unnecessary
power consumption.
operation mode. The system then restarts operation with the previous operation mode when the
circuit breaker is restored.
(26 ~ 28°C (78.8 ~ 82.4°F) in cooling, 20 ~ 24°C (68 ~ 75.2°F) in heating)
(T appears on the display to indicate that trial operation is selected.)
operation, press the [ON/OFF] button.
(2) (3) (4)
SiUS12-928_B
(3)
(2)
(2)
(1) (5)
(R14476)