SiUS12-928_B
2.4

Removal of Fan Motor

Procedure
Step
1
Remove the 2 lower
screws of the fan motor.
2
Remove the 2 upper
screws.
3
Remove the fan motor.
Removal Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
2
1
Fan motor
Outdoor Unit: 3MXS24JVJU, 4MXS32GVJU
(R10414)
 Be sure to remove the lower
screws first. If the upper
screws are removed first, the
fan motor may tilt or fall
because the center of its
gravity is toward the front.
It may cause injuries.
(R6442)
 When reassembling, be sure
to place the wire harness
lower.
(R10542)
Points
Harness
(R6444)