SiUS12-928_B
6.14 Compressor Sensor System Abnormality (24/32 Class
Only)
H0
Remote
Controller
Display
j
Outdoor Unit LED
A
Display
Fault condition is identified by the supply voltage and the DC voltage which is detected before
Method of
Malfunction
Fault condition is identified by the compressor current which is detected right after the
Detection
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
The detected value of the supply voltage and the DC voltage is obviously low or high.
Malfunction
The compressor current does not run when the compressor is started.
Decision
Conditions
Disconnection of reactor
Supposed
Disconnection of compressor harness
Causes
Defective outdoor unit PCB
Defective compressor
Service Diagnosis
i
i
h
h
1
2
3
4
the compressor startup.
compressor startup.
Troubleshooting for Outdoor Unit
174