Fluke PM2811 User Manual page 58

Programmable power supplies
Table of Contents

Advertisement

5 - 6
The following illustrations show the possible connections.
SERIES connection to increase the total output voltage capability:
+
V
1
+
V
2
WARNING:
Examples:
PARALLEL connection to increase the total output current capability:
I
1
+
V
1
Examples:
CAUTION:
+
V
L
load
O
I
A
load
D
P
load
-
To guarantee the safe use of the power supply, the total
maximum voltage at each terminal must not exceed 240V
with respect to ground.
• 2x 60V/2A = 120V/2A
• 2x 120V/1A= 240V/1A
• 2x 8V/15A = 16V/15A
I
2
+
V
2
• 2x 60V/2A = 60V/4A
• 2x 120V/1 = 120V/2A
• 2x 8V/15A =8V/30A
Only output channels with equivalent voltage and current
ratings may be connected in series or in parallel to prevent that
the channel with the lowest ratings will be damaged.
=V
+ V
1
2
= V
R
/
load
load
= V
x I
load
load
: maximum power = 240W
: maximum power = 240W
:maximum power = 240W
+
I
= I
L
load
O
V
A
load
D
P
load
-
: maximum power = 240W
: maximum power = 240W
: maximum power= 240W
Users Manual
+ I
1
2
=I
x R
load
load
=I
x V
load
load

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pm2812Pm2813Pm2831Pm2832

Table of Contents