F22 = 9 (Check weighing 3: Loss in weight)
Output and Condition
Relay HI,
1, -Net ≧ - (Final - Free fall)
Relay LO,
Relay OK*,
* Relay OK output can be changed to OVER or UNDER by setting F24.
Triangle 2 is displayed when Gross ≧ Full regardless of the F24 setting.
OVER/UNDER is judged always and the result is output to the display and the
relay.

11.2.2. Simple Batch

The weighing sequences of simple batch (F22=10, 11 or 12) are similar to those of
Check weighing (F22=7, 8 or 9) respectively. The differences are listed below.
1 Basically ON/OFF of the relay and the display is reversed.
2 No judgment other than Zero band and Full before input Start signal.
3 The weighing completion condition is set by F23: 2x and it is effective after Start.
4 The outputs of Preliminary and Free fall are off from weighing completion to the
next start.
5 Weighing completion can be output by setting F24 and F25.
6 The start signal can be accepted after weighing completion even if the weight is
not within the zero band.
7 Over/Under output is set by F23: 3x.
Start
Tare, when the Start is input automatically, if F23 is set to 11.
The READY mark turns off when the Start is input.
Weighing Completion
The weighing completion condition is set by F23: 2x.
F23 20 : Either the STOP key is pressed or the Batch stop input is on
F23 21 : Stable is detected after reaching Final
Before reaching Final, the STOP key or Batch stop input forces weighing
completion even if F23 is set to 21.
11.2. Setpoint Comparison
Weighing value
Calibrated Zero
3, Gross < Zero band
2, Gross ≧ Full
Tared Zero
Weighing
Free fall
OFF
ON
OFF
ON
OFF
Page 40
Preset target weight
Final
Tare
ON
ON
OFF
AD-4406 Weighing Indicator
Zero band
Time
OFF
OFF
ON