Zone Control; Overview - Emerson E2 Installation And Operation Manual

For rx refrigeration, bx hvac, and cx convenience store controllers
Hide thumbs Also See for E2:
Table of Contents

Advertisement

Inputs
Sensor Type
Outdoor Air Humid
Humidity
Curtailment Device
Digital
Fan Proof
Digital
Fan Proof Reset
Digital
VS Inverter Alarm
Digital
Enthalpy Switch
Digital
(Indoor and/or Out-
door)
Dewpoint Probe (for
Dewpoint
Economization)
Mixed Air Temp (ana-
Temperature
log economizers only)
Table 11-10
- Suction Group Inputs
Wire 8RO
Output Device
contacts to:
Heat / Cool Staged
see note
Outputs
Single-Speed Fans
see note
Two-Speed Fans
see note
(LOW, HIGH, and
fan contactor)
Digital Economizer
N.O.
Table 11-11
- Suction Group Outputs

11.7 Zone Control

11.7.1 Overview

An HVAC Zone is a collection of up to sixteen rooftop
units or air handling units that work together to maintain
the same temperature and humidity throughout a particular
Zone Control
Wiring
Instructions
Set up as Out-
door Humidity
Provider in
Global Data (see
Section 10.17
).
Set up as Curtail-
ment in Global
Sec-
Data (see
tion 10.17
).
See Table 9-1 on
page 9-3
See Table 9-1 on
page 9-3
See Table 9-1 on
page 9-3
See Table 9-1 on
page 9-3
See Table 9-1 on
page 9-3
See Table 9-1 on
page 9-3
Set Fail-safe Dip
Switch to:
see note
Set up any stages you want ON when the controller is off-line as
N.C. Stages you want OFF should be set as N.O.
see note
If one or more heat or cool stages will be ON, wire fan N.C. so
it will be active during controller off-line times. Otherwise, wire
N.O.
see note
If any heat or cool stages are configured to be ON (N.C.), set the
wiring and the switch to N.C., and set either the LOW or HIGH
stage output to N.C. (whichever speed you want active). If no
heat or cool will be active, set LOW, HIGH, and the fan contac-
tor to N.O.
N.O.
volume of space. The primary function of an HVAC Zone
is to "manage" the operation of each individual HVAC
unit by providing the temperature setpoints that will be
used in Temperature Control. Zones are also responsible
for ordering HVAC units to dehumidify and determining
when outside air conditions are favorable to economize.
Notes
Software Overview
-
11
25

Advertisement

Table of Contents
loading

Table of Contents