P/N
Sensor
207-1000
Refrigerant
Level Trans-
ducer (Hansen
Probe)
203-1902
Dewpoint Probe
Table 9-1
- Sensor Wiring
The 16AI, 8IO, and MultiFlex Inputs
Input Type
Dip Switch
Down
1. Wire BLACK ground
wire from "GND"
sensor terminal to odd
numbered board ter-
minal.
2. Wire GREEN signal
wire from "SIGNAL"
sensor terminal to
even numbered board
terminal.
3. Wire RED power wire
from "POWER" sen-
sor terminal to
+12VDC terminal on
board.
Up
1. Connect the WHITE
and GREEN wires to
AC1 and AC2 power
terminals.
2. Connect BLACK
ground wire to odd
numbered board termi-
nal.
3. Connect RED signal
wire to even numbered
board terminal.
Wiring