List 22: Two-Row Distribution Cabinet - Emerson SAG581126000 System Application Manual

Table of Contents

Advertisement

System Application Guide
Spec. No. 581126000 (Model 700
Controls a Low Voltage Battery Disconnect (LVBD) contactor located in an associated
Battery Stand.
The LVD circuit card provides three separate control circuits. Each control circuit can be programmed,
through the MCA, with its own disconnect voltage setpoint and one global reconnect setpoint. One LVD
circuit card can control up to four (4) contactors. Any contactor can be controlled by any of the three
control circuits on the card by setting of user-selectable switches.
Where more than one Distribution Cabinet contains an LVD control circuit card, the control circuits on all
LVD circuit cards can be set to any of the three MCA-controlled disconnect setpoints independently with
user-selectable switches.
Each of the three control circuits on any LVD card consists of two individual battery voltage monitors, both
of which must sense low system voltage before disconnection can occur. This redundancy prevents a
control circuit failure from unnecessarily disconnecting loads or batteries.
The user can set the low voltage disconnect circuits for either automatic or manual reconnect.
Automatic Reconnect: When system bus voltage recovers to a preset adjustable value, the low
voltage disconnect circuits automatically reconnect the loads (or battery) to the system bus.
Manual Reconnect: When system bus voltage has recovered to a preset adjustable value, the user
must issue a command via the MCA to reconnect loads (or battery) to the system bus.
A local switch provided in each Distribution Cabinet can be set to inhibit LVD operation for adjustment,
maintenance, and repair purposes. A local indicator illuminates when the low voltage disconnect circuit has
been inhibited. LVD operation is not inhibited in any other Distribution Cabinets in the power system.
Restrictions
Not available for
List 2
Cannot be ordered with
Ordering Notes
1) Order one (1) Distribution Bus Panel for each List 21 per
2) Order fuses and/or circuit breakers, as required, per
DESCRIPTIONS.
3) Order input and load distribution lugs, as required, per
DESCRIPTIONS.

List 22: Two-Row Distribution Cabinet

Features
♦ Accepts up to two (2) Distribution Bus Panels.
♦ Rated for up to 1000 amperes of distribution.
♦ Available for use in
♦ See also the description of the Quad Shunt circuit card under List
features.
♦ See also the description of the Low Voltage Disconnect circuit card under
List
21
features.
Restrictions
Not available for
List 2
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
)
NVBA
bays (no inter-bay busbar landings available).
List 1
if it is to be used with a
List 1
and
List 5
bays.
bays (no inter-bay busbar landings available).
Page 21 of 123
List
2.
'Distribution Bus
Arrangements'.
'Distribution
Devices' under ACCESSORY
'Wiring
Components' under ACCESSORY
21
SAG581126000
Issue AD, November 23, 2009