GJ/218-Type Circuit Breakers

Restrictions
A bus arrangement must be specified that contains GJ/218-type circuit breaker positions.
Load should not exceed 80% of device rating.
Refer to
Table 5
for required distribution row mounting positions.
Ordering Notes
1) Order circuit breakers as required per
2) Order a jumper kit as required for each circuit breaker per
Number
Mechanical Trip
Ampere
of
Rating
Positions
100
1
125
1
150
1
175
1
200
1
225
1
250
1
300
2
400
2
600
3
1, 2
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or manual trip condition.
2
Provides an alarm during an electrical trip condition only.
3
Extended shunt leads are 22 AWG stranded wire, approximately 7-10 ft. long from exit point at bottom of
Distribution Cabinet. Each shunt lead is equipped with a 49.9 ohm current limiting resistor.
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Table 5 (GJ/218 Circuit
GJ/218 Circuit Breakers
P/N
Electrical/
Electrical Trip
1
without
without
Internal Shunt
Internal Shunt
256621700
256621300
256621600
256621400
256621800
256622400
256621900
256622500
256622200
256622600
256622900
256622700
256623500
256623400
256625300
103572
256626200
256626300
256628200
103571
GJ/218 Circuit Breakers
Page 76 of 123
Spec. No. 581126000 (Model 700
Breakers).
Table 6 (Breaker Jumper
P/N
P/N
2
Electrical Trip
with
Internal Shunt
(25mV @ full
rated load)
516184
516187
516185
516186
516188
516189
516190
--
--
--
Table 5
System Application Guide
Kits).
P/N
2
Electrical/
1
Mechanical Trip
with
Internal Shunt
(25mV @ full
3
3
rated load)
123580
123631
123632
123633
123634
123635
123636
--
--
--
)
NVBA