List AB: Distribution Bus Module (P/N 428316100)
(3) GJ/218 Circuit Breaker System Positions
Features
♦ Single Voltage Distribution (+24V)
♦ 500A Maximum Capacity
♦ (3) Load Distribution Circuit Breaker Mounting Positions
(100 to 600A GJ/218-Type) NOTE RESTRICTIONS
Restrictions
Can be installed in bus positions A-C (row 1-3) of a 1-, 2-, 3-, or 4-bus row cabinet. Cannot be installed in bus
position D (row 4) of a 4-bus row cabinet. See also
Panel is designed to mount circuit breakers in the following possible combinations:
(3) 100A to 250A
(1) 100A to 250A and (1) 300A or 400A
(1) 600A
Ordering Notes
1) Order circuit breakers and associated jumper kits as required per Tables
2) Order load lugs (two hole, 3/8" bolt clearance hole, 1" centers) as required for each distribution position
per Table 10.
GROUND
BUSBAR
1"
1"
1"
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
LOAD
CONNECTIONS
LOAD RETURN
CONNECTIONS
1.5"
LOADS
Page 34 of 123
Spec. No. 581126000 (Model 700
List AC
for similar application in bus position D (row 4).
3/8-16 CAPTIVE NUT, 12 PLACES
(CUSTOMER MUST SUPPLY LUG
BOLTS AND ADDITIONAL
HARDWARE. BOLT LENGTH: 1-1/4")
1"
System Application Guide
5
and 6.
)
NVBA