Emerson SAG581126000 System Application Manual page 102

Table of Contents

Advertisement

SAG581126000
Issue AD, November 23, 2009
(E) High Voltage Alarm 2: Adjustable from 24.00 to 29.50 volts DC. Factory set as
follows, unless otherwise specified.
Power System List No.
MCA Configuration No.
Factory Setting (Volts)
(F) Battery On Discharge Alarm: Adjustable from 20.00 to 28.00 volts DC. Factory set as
follows, unless otherwise specified.
Power System List No.
MCA Configuration No.
Factory Setting (Volts)
(G) 50% Battery On Discharge (Very Low Voltage) Alarm: Adjustable from 20.00 to 28.00
volts DC. Factory set per table below, unless otherwise specified.
Power System List No.
MCA Configuration No.
Factory Setting (Volts)
(H) System Load Current Alarm: Adjustable from 0 to 60,000 amperes. Factory set at 2,000
amperes, unless otherwise specified.
(I) Subsystem High Voltage Alarm (if subsystem installed): Adjustable from 0.00 to 60.00
volts DC. Factory set as follows, unless otherwise specified.
Power System List No.
MCA Configuration No.
Factory Setting (Volts)
(J) Subsystem Low Voltage Alarm (if subsystem installed): Adjustable from 0.00 to 60.00
volts DC. Factory set as follows, unless otherwise specified.
Power System List No.
MCA Configuration No.
Factory Setting (Volts)
(K) Subsystem Load Current Alarm (if subsystem installed): Adjustable from 0 to 60000
ampere. Factory set at 2000 amperes, unless otherwise specified.
(L) High Battery Ambient Temperature Alarm (if battery charge digital temperature
compensation probe or TXM installed): Adjustable from -50°C to +99°C. Factory set to
off, unless otherwise specified. (If TXM installed, each temperature probe has an associated
alarm.)
(M) Low Battery Ambient Temperature Alarm (if battery charge digital temperature
compensation probe or TXM installed): Adjustable from -49°C to +100°C. Factory set to
off, unless otherwise specified. (If TXM installed, each temperature probe has an associated
alarm.)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
10
11
534876
534877
28.25
28.50
10
11
534876
534877
24.00
23.50
10
11
534876
534877
23.00
22.00
10
11
534876
534877
50.00
53.00
10
11
534876
534877
46.00
44.50
Page 102 of 123
System Application Guide
Spec. No. 581126000 (Model 700
12
13
534878
534879
28.25
28.25
12
13
534878
534879
24.00
24.00
12
13
534878
534879
23.00
23.00
12
13
534878
534879
50.00
50.00
12
13
534878
534879
46.00
46.00
)