Assembly - Emerson SAG581126000 System Application Manual

Table of Contents

Advertisement

SAG581126000
Issue AD, November 23, 2009
Connections to Inter-bay Busbars (P/O List 2)
Note: Battery busbars within distribution cabinets are rated for 2000A max.
For 2000A-4000A in List 2, make battery connections to inter-bay busbars, shown here.
Battery Lug
Landing Points
See Detail A
Rear View
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
GND RETURN
Interbay Busbar Assembly
+24V SUPPLY
Interbay Busbar Assembly
3/8-16 CAPTIVE NUT, 8 PLACES PER BUS
(CUSTOMER MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")
2-3/8"
13/16"
1"
1-5/8"
1/4-20 CAPTIVE NUT, 12 PLACES PER BUS
(CUSTOMER MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")
Page 118 of 123
System Application Guide
Spec. No. 581126000 (Model 700
2-3/8"
2-3/8"
13/16"
13/16"
13/16"
3/4"
3/4"
3/4"
1-5/8"
DETAIL A
)
NVBA