List Nb: Distribution Bus Module (P/N 513809) (3) Gj/218 Circuit Breaker Battery Disconnect Positions - Emerson SAG581126000 System Application Manual

Table of Contents

Advertisement

SAG581126000
Issue AD, November 23, 2009
List NB: Distribution Bus Module (P/N 513809)
(3) GJ/218 Circuit Breaker Battery Disconnect Positions
Features
♦ Single Voltage Distribution (+24V)
♦ 500A Maximum Capacity
♦ (3) Battery Disconnect Circuit Breaker Mounting Positions
(100 to 600A GJ/218-Type) NOTE RESTRICTIONS
Restrictions
Limit one bus arrangement of this type per Distribution Cabinet.
Must be installed in bus position A or B (row 1 or 2) of a 1-, 2-, 3-, or 4-bus row cabinet.
Cannot be used in second row of a 3-bus row cabinet in List 1 if used with List 2.
Cannot be used in second row of a 3-bus row cabinet in List 2.
Panel is designed to mount circuit breakers in the following possible combinations:
(3) 100A to 250A
(1) 100A to 250A and (1) 300A or 400A
(1) 600A
Ordering Notes
1) Order circuit breakers and associated jumper kits as required per Tables
2) Order battery lugs (two hole, 3/8" bolt clearance hole, 1" centers) as required for each distribution position
per Table 10.
BATTERY (LOAD SIDE)
1"
1"
1"
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
CONNECTIONS
BATTERY DISCONNECT
Page 62 of 123
Spec. No. 581126000 (Model 700
3/8-16 CAPTIVE NUT, 6 PLACES
(CUSTOMER MUST SUPPLY LUG
BOLTS AND ADDITIONAL
HARDWARE. BOLT LENGTH: 1-1/4")
System Application Guide
5
and 6.
)
NVBA
Home

Advertisement

Table of Contents
loading

Table of Contents